Papua New Guinea SG17/20/23/25T-CN

High conversion efficiency, wide working voltage range, early start and late stop, efficient power generation more lasting
The maximum input voltage is 1100V, which can be connected to more solar panels, and the estimated power generation can be increased by about 2%.
Maximum support 18A current, perfectly compatible with 182 and 210 components

Category:

Papua New GuineaSolar Inverter

Product Description

Technical parameters

Input (DC)

  SG17T-CN SG20T-CN SG23T-CN SG25T-CN
Maximum input voltage: 1100 V 1100 V 1100 V 1100 V
Minimum input voltage/starting voltage: 160 V/180 V 160 V/180 V 160V/180V 160 V/180 V
Rated input voltage: 600 V 600 V 600 V 600 V
MPPT voltage range: 160 V-1000 V 160V-1000V 160V-1000V 160V-1000V
Maximum number of MPPT input strings per channel: 2/1 2/1 2/1 2/1
Maximum input current per channel: 36 A / 18 A 36 A / 18 A 36 A/ 18 A 36 A/ 18 A
Maximum input current: 54A(36 A/18A) 54A(36A/18A) 54A(36A/18A) 54A(36A/18A)
MPPT Quantity: 2 2 2 2
Maximum allowable current of input terminal: 20 A 20 A 20 A 20 A
Maximum DC short circuit current: 60A(40 A/20A) 60A(40 A/20A) 60A(40 A/20 A) 60A(40A/20 A)

 Input (AC)

  SG17T-CN SG20T-CN SG23T-CN SG25T-CN
Rated output power: 17000 W 20000 W 23000 W 25000 W
Maximum output power: 18700 W 22000 W 25300 W 27500 W
Maximum output apparent power: 18700 and pad 22000 and pad 25300 and pad 27500 and pad
Maximum output current: 28.3 A 31.9 A 36.7 A 39.9 A
Rated grid voltage: 3/N/PE,230 V/400 V,220 V/380 V 3/N/PE, 230 V/400 V, 220 V/380 V 3/N/PE,230 V/400V, 220 V/380 V 3 /N/PE, 230 V/400 V,220 V/380 V
Grid voltage range: 156V-300V (phase voltage) 156V-300V (phase voltage) 156V-300V (phase voltage) 156V-300V (phase voltage)
Rated grid frequency/grid frequency range: 50 Hz/45 H-55 Hz 50Hz/45Hz-55Hz 50Hz/45Hz-55Hz 50Hz/45Hz-55Hz
total current waveform distortion rate: <3% (at rated power) <3% (at rated power) <3% (at rated power) <3% (at rated power)
DC component: <0.5 % In <0.5% In <0.5 % In <0.5 %In
Power factor: > 0.99 (at rated power) > 0.99 (at rated power) > 0.99 (at rated power) > 0.99 (at rated power)
power factor adjustable range: 0.8 lead -0.8 lag 0.8 lead -0.8 lag 0.8 lead -0.8 lag 0.8 lead -0.8 lag
Feed phase number/output phase number: 3/3-N-PE 3/3-N-PE 3/3-N-PE 3/3-N-PE

Efficiency

  SG17T-CN SG20T-CN SG23T-CN SG25T-CN
Maximum efficiency: 98.3 % 98.3 % 98.5 % 98.6 %
Efficiency in Europe: 98.1 % 98.1 % 98.1 % 98.1 %

Protection and Function

  SG17T-CN SG20T-CN SG23T-CN SG25T-CN
DC reverse connection protection: Have Have Have Have
AC Short Circuit Protection: Have Have Have Have
Leakage current protection: Have Have Have Have
Grid monitoring: Have Have Have Have
DC Switch: Have Have Have Have
Group string detection: Have Have Have Have
Island Protection: Have Have Have Have
Surge protection: DC secondary/AC secondary DC secondary/AC secondary DC secondary/AC secondary DC secondary/AC secondary

General Parameters

  SG17T-CN SG20T-CN SG23T-CN SG25T-CN
Size (width * height * depth) 410 mm*530 mm*208 mm 410 mm* 530 mm * 208 mm 410 mm * 530 mm * 208 mm 410 mm* 530 mm* 208 mm
Weight: 21 kg 21 kg 21 kg 21 kg
Isolation mode: No transformer No transformer No transformer No transformer
Protection class: IP65 IP65 IP65 IP65
Night loss: ≤ 1W ≤ 1W ≤ 1W ≤ 1W
Operating temperature range: -25 ℃-60 ℃ -25 ℃-C-60 ℃ -25 ℃-60 ℃ -25 ℃-60 ℃
Operating humidity range 0%-100 (no condensation) 0%-100 (no condensation) 0%-100 (no condensation) 0%-100 (no condensation)
Cooling mode Intelligent air cooling Intelligent air cooling Intelligent air cooling Intelligent air cooling
Maximum working altitude: 4000 m 4000 m 4000 m 4000 m
Noise: <50 dB <50 dB <50 dB <50 dB
Display: LED, APP LED, APP LED, APP LED, APP
Communications: 4G 4G 4G 4G
DC terminal type MC4 compatible terminal MC4 compatible terminal MC4 compatible terminal MC4 compatible terminal
AC terminal type OT/DT terminal OT/DT terminal OT/DT terminal OT/DT terminal
Compliance with standards: NB/T 32004-2018,GB/T 37408-2019 NB/T 32004-2018,GB/T 37408.2019 NB/T 32004-2018,GB/T 37408-2019 NB/T 32004-2018,GB/T 37408-2019
Grid Support: Anti-islanding, active and reactive power regulation, PF control: slow start/shutdown Anti-islanding, active and reactive power regulation, PF control, slow start/shutdown Anti-islanding, active and reactive power regulation, PF control, slow start/shutdown Anti-islanding, active and reactive power regulation, PF control, slow start/shutdown