south sudan republic SG33/50CX-P2-CN
Adaptive weak grid, grid-friendly and high yield.
15A DC side input, can adapt to 500W large components
Wide working voltage range, early start, late shutdown, more lasting power generation
15A DC side input, can adapt to 500W large components
Wide working voltage range, early start, late shutdown, more lasting power generation
Category:
south sudan republicSolar Inverter
Product Description
Technical parameters
Input
| SG33CX-P2-CN | SG50CX-P2-CN | |
| Maximum input voltage: | 1100V | 1100V |
| Minimum input voltage/starting voltage: | 160V/200V | 160V/200V |
| Rated input voltage: | 600V | 600V |
| MPPT voltage range: | 160-1000V | 160-1000V |
| Maximum number of MPPT input strings per channel: | 2 | 2 |
| Maximum input current per channel: | 15A | 15A |
| Maximum input current: | 90 A(3x30A) | 90 A(3x30A) |
| MPPT Quantity: | 3 | 4 |
| Maximum allowable current of input terminal: | 30A | 30A |
| Maximum DC short circuit current: | 120A(3X40A) | 160A(4X40A) |
Output
| SG33CX-P2-CN | SG50CX-P2-CN | |
| Rated output power: | 33000 W | 50000 W |
| Maximum output power: | 36300 W | 55000 W |
| Maximum output apparent power: | 36300 and pad | 55000 and pad |
| Maximum output current: | 55.2 A | 83.6 A |
| Rated grid voltage: | 3/N/PE, 230/400 V, 220/380V | 3/N/PE,230/400V,220/380 V |
| Grid voltage range: | 312-480V | 312-480V |
| Rated grid frequency/grid frequency range: | 50 Hz/45~55 Hz | 50 Hz/45~ 55 Hz |
| total current waveform distortion rate: | <3% (at rated power) | <3% (at rated power) |
| DC component: | <0.5%In | <0.5 % In |
| Power factor: | > 0.99 (at rated power) | > 0.99 (at rated power) |
| power factor adjustable range: | 0.8 lead ~ 0.8 lag | 0.8 lead ~ 0.8 lag |
| Number of feed phases/number of output phases: | 3/3 | 3/3 |
Efficiency
| SG33CX-P2-CN | SG50CX-P2-CN | |
| Maximum efficiency | 98.60% | 98.52% |
| Efficiency in China | 98.08% | 98.00% |
Protection
| SG33CX-P2-CN | SG50CX-P2-CN | |
| DC reverse connection protection: | Have | Have |
| AC Short Circuit Protection: | Have | Have |
| Leakage current protection: | Have | Have |
| Grid monitoring: | Have | Have |
| DC Switch: | Have | Have |
| Group string detection: | Have | Have |
| Island Protection: | Have | Have |
| Surge protection: | DC secondary/AC secondary | DC secondary/AC secondary |
General Parameters
| SG33CX-P2-CN | SG50CX-P2-CN | |
| Dimensions (width x height x depth) | 605*575*245mm | 605*575*245mm |
| Weight: | 35kg | 38kg |
| Isolation mode: | No transformer | No transformer |
| Protection class: | IP66 | IP66 |
| Night loss: | ≤ 1W | ≤ 1W |
| Operating temperature range: | -30~60℃C | -30~60℃C |
| Operating humidity range (non-condensing): | 0~100% | 0~100% |
| Cooling method: | Intelligent forced air cooling | Intelligent forced air cooling |
| Maximum working altitude: | 4000m(>2000m derating) | 4000m(>2000m derating) |
| Display: | LED, Bluetooth APP | LED, Bluetooth APP |
| Communications: | 4G | RS485 * 2,4G |
| DC terminal type: | MC4 | MC4 |
| AC terminal type: | OT/DT terminal (max. 35mm2) | OT/DT terminal (max. 50mm2) |
| Conform to the standard: | NB/T 32004-2018,GB/T 37408-2019 | NB/T 32004-2018,GB/T 37408-2019 |
| Grid Support: | Anti-islanding, active and reactive power regulation, PF control, slow start/shutdown | Anti-islanding, active and reactive power regulation, PF control, slow start/shutdown |